Danfoss · VLT AutomationDrive FC 301/302
This alarm indicates a potential issue related to the compressor. The manual suggests it might not be a direct compressor or drive failure itself but a symptom of another problem, requiring further investigation to determine the root cause. This fault prevents the system from operating correctly.
Click steps to track your progress.
Isolate power, then measure motor winding resistance between phases U, V, W for continuity and balanced values (e.g., ±5% tolerance).
Check for mechanical free movement of the compressor shaft (if accessible and safe) to identify internal binding or seized components.
Verify discharge pressure transducer (e.g., PT-1) readings against actual system pressure using a calibrated gauge to confirm accuracy.
Inspect lubrication oil level and quality (e.g., contamination, viscosity) according to OEM specifications for the compressor model.
Check drive parameters P1-05 (Motor Rated Current) and P2-01 (Overload Trip Level) are set correctly for the compressor motor's nameplate data.