Danfoss · VLT AutomationDrive FC 301/302
The system has initiated a safe stop due to the High Pressure (HP) switch tripping. This indicates that the system's internal pressure has exceeded its safe operating limits, triggering a protective shutdown to prevent damage to the compressor or other components within the refrigeration circuit. The system will not operate until this condition is cleared.
Click steps to track your progress.
Verify the reading of the discharge pressure transducer (e.g., PT-1) against a calibrated mechanical pressure gauge at the high-pressure side.
Inspect the condenser coils for dirt, debris, or obstructions blocking airflow; clean as necessary using appropriate methods.
Check the operation of the condenser fan motor(s) (e.g., M2) and verify correct rotation and airflow volume.
Measure the opening/closing pressure of the High Pressure (HP) switch (e.g., PS-2) using a controlled pressure source and verify its setting (if adjustable).
Check for any closed manual isolation valves (e.g., V10) or damper positions in the discharge piping that could restrict flow.