Danfoss · VLT AutomationDrive FC 301/302
If the DC-link voltage exceeds a specific limit, the frequency converter will trip after a certain time delay. This typically occurs due to regenerative energy from the motor during deceleration or an issue with the mains supply.
Click steps to track your progress.
Measure the incoming AC line-to-line voltage at the drive's input terminals (e.g., L1-L2, L2-L3, L3-L1) and confirm it is within nominal limits.
Increase the deceleration ramp time (e.g., P3-42 Decel Ramp Time) to allow slower dissipation of regenerative energy.
Measure the resistance of the external brake resistor (e.g., terminals 81, 82) and compare it to the specified value.
Verify that the brake chopper circuit is correctly switching by observing current flow through the brake resistor during regeneration.
Check parameter P2-13 (Brake Power Monitoring) and adjust to option [1] Warning if continuous operation with warning is acceptable.