Danfoss · VLT AutomationDrive FC 301/302
A parameter has been configured with a value that falls outside its acceptable minimum or maximum range. This prevents the drive from operating correctly and can lead to unexpected behavior.
Click steps to track your progress.
1. Identify the specific parameter number (e.g., P1-03) and its invalid value that triggered the fault, usually displayed on the LCP.
2. Navigate to the identified parameter (e.g., P1-03) on the LCP and adjust its value to be within the specified minimum and maximum limits (e.g., 0-3600 rpm).
3. If the parameter was set via a fieldbus, verify the PLC/controller logic that is writing to the drive's parameter address.
4. Perform a factory reset (P8-01 to [1] Factory reset) to restore all parameters to their default values (record current settings first).
5. If the fault occurs after loading a parameter backup, review the backup file for any parameter values that exceed limits for the current drive model or firmware.