Danfoss · VLT AutomationDrive FC 301/302
The frequency converter has been operating at more than 100% overload for an excessive period and is about to trip. A warning is issued at 98% overload, and a trip (alarm) occurs at 100%. The frequency converter cannot be reset until the internal thermal counter drops below 90%.
Click steps to track your progress.
Measure the actual motor current (e.g., with clamp meter on U, V, or W output phases) and compare to motor nameplate and P1-20.
Verify the motor's mechanical load by manually turning the shaft (if possible) for unusual resistance or friction.
Cross-check all motor parameters in the drive (e.g., P1-20 to P1-25) against the motor nameplate data.
Inspect the drive's internal and external cooling fans for proper operation and ensure unobstructed air circulation.
Increase the drive's acceleration and deceleration ramp times (P3-41, P3-42) to reduce peak currents during transients.
Consider upsizing the motor or drive if continuous current remains above 95% of rated current under normal load.