Danfoss · VLT HVAC Drive FC 102
A direct short circuit exists in the motor windings or the motor wiring connected to the frequency converter's output terminals. This is a critical fault that can cause immediate and severe damage to the frequency converter's output stage if power is not removed quickly. Continued operation is highly dangerous.
Click steps to track your progress.
Disconnect the motor cables from the drive's output terminals (U, V, W).
Measure the resistance between each pair of motor output terminals (U-V, V-W, U-W) at the drive's output side of the cable; readings should be balanced and non-zero (not 0 Ohms).
Perform an insulation resistance test (Megger) between each motor phase to ground and between phases at the motor terminal box to detect insulation breakdown.
Visually inspect the motor connection box and cable terminations for signs of arcing, carbon tracking, or conductive foreign material.