Danfoss · VLT HVAC Drive FC 102
The connected braking resistor has been detected as short-circuited. This prevents proper energy dissipation during braking, potentially damaging the drive's braking chopper or causing overvoltage trips during deceleration.
Click steps to track your progress.
1. Power off the drive and disconnect the braking resistor wiring from the drive's terminals (e.g., R+ and R-).
2. Measure the resistance across the braking resistor terminals using a multimeter. Compare the reading to the nominal resistance specified (e.g., 20 Ohms). A near-zero reading indicates a short.
3. Visually inspect the resistor wiring for damaged insulation, frayed conductors, or accidental bridging between conductors.
4. Check the resistor terminals and enclosure for conductive dust, metal shavings, or moisture that could cause a short.
5. Replace the braking resistor unit if the measured resistance is significantly below its specified nominal value, indicating an internal short circuit.