Danfoss · VLT HVAC Drive FC 102
Too many power-ups have occurred within a short time period, leading to excessive inrush current events. This frequent power cycling prevents the unit from dissipating heat and can stress internal components, potentially shortening the drive's lifespan.
Click steps to track your progress.
1. Monitor the mains supply voltage for stability and absence of rapid on/off cycles for at least 5 minutes.
2. Inspect the drive's internal pre-charge circuit (resistors and bypass contactor) for physical damage or wear.
3. Verify the operation of the external main input contactor; check coil voltage and contact integrity.
4. Ensure the drive remains powered down for a minimum of 10 minutes between consecutive power cycles to allow capacitor discharge.