Danfoss · VLT HVAC Drive FC 102
The frequency converter has detected a loss of incoming supply voltage, and the 'Mains Failure' parameter (14-10) is configured to generate an alarm. This indicates a power supply interruption to the drive, which will cause the motor to stop. Until mains power is restored, the drive cannot operate.
Click steps to track your progress.
1. Check all upstream fuses and circuit breakers in the main power distribution panel.
2. Measure the incoming line-to-line and line-to-neutral voltages at the drive's L1, L2, L3 input terminals.
3. Verify the setting of parameter 14-10 (Mains Failure Function) to ensure it aligns with operational requirements.
4. Inspect all main power wiring connections at the drive for tightness, corrosion, or signs of overheating.