EL
ErrorLib
Brands
||
  1. Home
  2. Danfoss
  3. VLT HVAC Drive FC 102
  4. 38.1316
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

38.1316

Internal Fault: Option software in slot B not supported

Danfoss · VLT HVAC Drive FC 102

What does 38.1316 mean?

The software on the option card installed in slot B is not recognized or supported by the frequency converter's firmware. This indicates a fundamental incompatibility, preventing the option card from integrating correctly with the drive's control system.

Common Causes

  • Installation of an option card in slot B with unsupported or incompatible software (e.g., beta firmware, custom modification).
  • The drive's main firmware version is too old to recognize or interface with the software on the installed option card.
  • Corruption of the option card's firmware, rendering it unreadable or unrecognizable by the main drive.
  • Attempting to use an option card from a different product series or manufacturer that is physically installed but logically incompatible.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Record the exact model number and part number of the option card installed in slot B.

  2. 2

    2. Verify the frequency converter's main firmware version via the LCP (parameter 15-00) or manufacturer software.

  3. 3

    3. Refer to the manufacturer's compatibility matrix or documentation to confirm that the option card's software is officially supported by the drive's current firmware version.

  4. 4

    4. If compatibility is confirmed, attempt to re-flash the option card's firmware with the latest officially supported version using manufacturer software.

  5. 5

    5. If incompatibility is identified, replace the option card in slot B with a supported model, or update the main drive firmware if the option card is newer and requires it for compatibility.

Browse all codes in this manual (75)
Verified technical data. Last updated: April 2026

Related Faults

110 Volts low10Motor overload temperature11Motor thermistor over temp
Source: Danfoss VLT HVAC Drive FC 102
View Official PDFSearch more codes in this manual