Danfoss · VLT HVAC Drive FC 102
An internal parameter's stored value has fallen outside its predefined minimum or maximum allowable range. This can be caused by data corruption, an incorrect parameter write, or a software anomaly, leading to unexpected drive behavior or shutdown.
Click steps to track your progress.
1. Cycle power to the frequency converter to force a re-initialization of internal parameter registers.
2. Perform a parameter initialization (P14-22 set to '2') to revert all parameters to factory defaults.
3. Reload a known good parameter backup from a saved configuration file or a different drive.
4. Update the drive's firmware to the latest available version, as this can resolve known parameter handling bugs.