Danfoss · VLT HVAC Drive FC 102
The intermediate circuit voltage (DC) has risen above the high-voltage warning limit, which is dependent on the frequency converter's voltage rating. The unit is still active, but operating at an elevated voltage could stress internal components or lead to a trip if limits are exceeded.
Click steps to track your progress.
Measure the incoming AC mains voltage at terminals L1, L2, L3 to verify it is within the frequency converter's specified operating range.
Increase the deceleration ramp time in parameter P3-42 (Ramp Down Time 1) or P3-43 (Ramp Down Time 2) to reduce regenerative energy generation.
Verify the braking resistor connection (terminals 81, 82) and measure its resistance (in Ohms) to ensure it matches the drive's specifications.
Inspect the braking chopper circuit for proper function; measure voltage across braking resistor terminals (81, 82) during deceleration (power ON).