Danfoss · VLT HVAC Drive FC 102
The Automatic Motor Adaptation (AMA) process was intentionally stopped by the user. If this was unintentional, it means AMA did not complete its motor characterization. This will prevent the drive from optimizing motor control and protection based on the motor's actual electrical properties.
Click steps to track your progress.
Confirm if the interruption was intentional; if unintentional, identify the source of the interruption.
Ensure no digital inputs configured for stop or reset functions (e.g., P5-10 Terminal 18 Digital Input) are active during AMA.
Verify that stable control power (e.g., at terminals 12, 13) is maintained throughout the entire AMA execution.
If controlled via fieldbus, check for communication errors, network cable integrity, or timeouts from the master controller.
Re-initiate the AMA process (P1-29 Motor Adaptation) and closely observe the drive to prevent accidental interruption.