Danfoss · VLT HVAC Drive FC 102
The intermediate circuit voltage (DC) has dropped below the low-voltage warning limit, which is dependent on the frequency converter's voltage rating. The unit is still active, but operating with insufficient voltage could affect performance or lead to a trip.
Click steps to track your progress.
Measure the incoming AC mains voltage at terminals L1, L2, L3 under load to confirm it stays within the frequency converter's specified operating range.
Verify the sizing of upstream circuit breakers and contactors to ensure they are not causing voltage drops under motor load.
Tighten all power connections at the drive input terminals (L1, L2, L3) and inspect for signs of corrosion or arcing.
Review parameter P1-20 (Mains Voltage) to ensure it is correctly set to the actual incoming supply voltage for accurate monitoring.