Danfoss · VLT HVAC Drive FC 102
A digital input signal has indicated an external fault condition, causing the frequency converter to trip. This means an external safety or control system has commanded the drive to stop due to a detected issue. The external fault must be cleared before normal operation can resume.
Click steps to track your progress.
Identify which digital input (e.g., Terminal 18, 19, 27) is configured for the external interlock function (refer to P5-10 to P5-15).
Verify the physical status of the external safety device or control system connected to the identified digital input.
Measure the voltage at the relevant digital input terminal to confirm the signal status (e.g., 24VDC for active, 0VDC for inactive).
Check the wiring integrity from the external device to the drive's digital input terminals for shorts, opens, or loose connections.
Review the drive's event log (P15-30 Fault Log) for additional information about which input triggered the fault.
Temporarily disable the interlock function in parameters (e.g., P5-10 set to 'No operation') for troubleshooting, only if safe and permissible.