Danfoss · VLT HVAC Drive FC 102
If the intermediate circuit voltage (DC link) drops below the under-voltage limit, the frequency converter checks for a 24 V DC back-up supply. If no back-up is connected, the unit trips after a fixed delay. This condition can lead to unexpected shutdowns and loss of motor control.
Click steps to track your progress.
Measure the incoming AC mains voltage at terminals L1, L2, L3 to verify it remains above the minimum specified operating voltage during operation.
Inspect all fuses and circuit breakers in the supply path to the drive; replace blown fuses or reset tripped breakers.
Tighten all power wiring connections at the drive's input terminals (L1, L2, L3) and inspect for signs of arcing or corrosion.
If 24VDC backup is used, verify the backup supply voltage at terminals 12 and 13, and check its current capacity against drive requirements.