Danfoss · VLT HVAC Drive FC 102
The frequency converter is operating with an excessively high current for too long, nearing its thermal protection limit. The electronic thermal inverter protection counter issues a warning at 98% and an alarm trip at 100%. The unit cannot be reset until the counter drops below 90%, indicating a significant risk of damage to the inverter if prolonged.
Click steps to track your progress.
Measure the actual output current to the motor using a clamp meter on one of the output phases (U, V, W) and compare it against the drive's rated current.
Verify parameter P1-02 (Motor Current) and P1-03 (Motor Speed) are correctly set according to the motor's nameplate data.
Mechanically inspect the driven load for obstructions, excessive friction, or misalignment that could increase torque requirements.
Increase acceleration and deceleration ramp times in parameters P3-41 (Ramp Up Time 1) and P3-42 (Ramp Down Time 1) to reduce peak currents.