Danfoss · VLT HVAC Drive FC 102
A no-flow condition has been detected in the system, and parameter 22-23 (No-Flow Function) is set to trigger an alarm. This indicates a critical deviation in the process, such as a pump running dry or a blocked pipe. Continued operation in a no-flow state can damage pumps or other system components.
Click steps to track your progress.
1. Visually inspect the process system (e.g., pump inlet/outlet, valves, reservoir level) for any obvious no-flow conditions.
2. Verify the signal from the flow sensor at the drive's analog input (e.g., terminal 53) using a multimeter.
3. Review and adjust parameter 22-23 (No-Flow Function) threshold and delay settings to suit the application's characteristics.
4. Check for any physical blockages in the pipework or strainers upstream and downstream of the pump.