Danfoss · VLT HVAC Drive High Power
This warning/alarm indicates a loss of communication with the frequency converter. It becomes active when parameter 8-04 Control Word Timeout Function is not set to [0] Off. If configured to [2] Stop and [26] Trip, the frequency converter will ramp down and then trip into an alarm state, indicating a critical communication failure.
Click steps to track your progress.
Verify the status of the master controller (PLC/DCS) program execution and communication diagnostics.
Check the status indicator LEDs on the frequency converter's communication module for communication activity and errors.
Inspect the communication cable connections at both the frequency converter and the master controller for proper seating and damage.
Measure continuity of communication cable pairs (e.g., EtherNet/IP RX/TX pairs) using a cable tester.
Confirm parameter 8-04 Control Word Timeout Function is set to the desired value (e.g., [2] Stop or [1] Freeze output) for the application.
If using a fieldbus, verify the network configuration (e.g., IP address, node ID, baud rate) matches the master controller settings.