Fanuc · AC Spindle Motor Alpha i-Beta i Series Parameters
A time-out was detected in communication with a serial spindle amplifier for Series 15i. This indicates a delay or failure in receiving a response from the amplifier within the expected timeframe.
Click steps to track your progress.
Verify the presence of data activity on the serial communication bus using an oscilloscope.
Set parameter P1-54 to the correct baud rate and protocol settings for the amplifier.
Power cycle the spindle amplifier and the CNC.
Inspect the serial cable for physical damage and ensure secure connections at both ends.
Measure the voltage at the serial communication terminals (e.g., T+, T-, R+, R-) on the CNC side.