SRVO-071

Abnormally High Feedback Speed

Fanuc · R-30iB Mate + Mate Plus Robot

What does SRVO-071 mean?

The feedback speed reported by the motor's Pulsecoder is abnormally high, exceeding expected operational limits. If this alarm occurs concurrently with the SRVO-064 (PHAL alarm), SRVO-064 is considered the primary cause.

Common Causes

  • Axis moving at an unexpectedly high speed indicated by the pulsecoder feedback.
  • External force causing rapid unintended axis movement.
  • Incorrect servo motor command or velocity loop tuning.
  • Pulsecoder generating erroneous high-speed feedback due to internal fault.
  • Mechanical resonance causing rapid oscillation of the axis.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Ensure the robot connection cable (RMP1, RP1) connector (CRF8) on the 6-Axis servo amplifier and the connector on the motor side are tightly connected.

  2. 2

    Check that the shielding of the robot connection cable (RMP1, RP1) is securely grounded in the cabinet.

  3. 3

    Replace the Pulsecoder.

  4. 4

    Replace the servo amplifier.

  5. 5

    Replace the robot connection cable (RMP1, RP1, RM1).

  6. 6

    Replace the internal cable of the robot (for the Pulsecoder, or for the Motor).

Browse all codes in this manual (53)