SRVO-105

Door Open or Emergency Stop

Fanuc · R-30iB Mate + Mate Plus Robot

What does SRVO-105 mean?

This alarm indicates that the cabinet door is open or an emergency stop condition is active, triggering a safety interlock. This prevents robot operation until the safety condition is resolved, ensuring operator and equipment safety.

Common Causes

  • External emergency stop button activated.
  • Safety interlock switch for a door is open.
  • Internal safety circuit fault in the control panel.
  • Configuration error for safety inputs (e.g., P5-01).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    If an auxiliary cabinet (option) is installed, check whether its door is open and ensure it is securely closed.

  2. 2

    If an auxiliary cabinet is installed, check the door switch and its wiring for faults; replace if necessary.

  3. 3

    Check that the CRMA92 and CRMB8 connectors on the E-STOP unit and the CRMA91 connector on the 6-Axis servo amplifier are connected securely.

  4. 4

    Replace the emergency stop board.

  5. 5

    Replace the 6-Axis servo amplifier.

Browse all codes in this manual (53)
Verified technical data. Last updated: April 2026