Fanuc · Series 0i-D/0i Mate-D Maintenance
This warning signal on the Fanuc Series 0i-D/0i Mate-D αi servo system indicates a failure of the converter cooling fan. This condition (SVWRN4 and SVWRN3 active) will lead to a converter overheat alarm if not addressed.
Click steps to track your progress.
Visually inspect the converter cooling fan for any blockages from dust or debris, and check for physical damage to the blades.
Verify the power connections to the converter fan for tightness and absence of corrosion.
Observe the fan's operation during power-on; check for proper rotation and absence of abnormal noise.
Ensure that the air passages for the converter cooling are clear and unrestricted.
If the fan is determined to be defective or not functioning, replace the converter cooling fan unit.