DS0300

APC ALARM: NEED REF RETURN

Fanuc · Series 30i/31i/32i-MODEL B Parameter

What does DS0300 mean?

This alarm indicates that the correspondence between the machine position and the absolute position detector (absolute Pulsecoder or rotary scale with distance-coded reference marks) has been lost. This condition sets bit 4 (APZ) of parameter No. 1815 to 0. A reference position return is required to re-establish the absolute position. The specific cause is further detailed in diagnostic data No. 310#0.

Common Causes

  • Alarm from the APC system indicating a need for reference return.
  • Encoder or sensor data lost, requiring re-homing.
  • Axis position lost, necessitating recalibration.
  • Home position signal not received.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Perform a reference position return for the affected axis.

  2. 2

    Check diagnostic data No. 310#0 for a detailed cause code related to the APC alarm.

  3. 3

    After successfully performing the reference return, verify that bit 4 (APZ) of parameter No. 1815 is automatically set back to 1.

Browse all codes in this manual (12)
Verified technical data. Last updated: April 2026

Related Faults

DS0016Scale Zero Point/Base Point Distance Out of RangeDS1448Scale Zero Point/Base Point Distance Out of RangeER54NC-PMC I/F ASSIGNMENT ERROR
Source: FANUC Series 30i/31i/32i-MODEL B Parameter
Open Manual (Page 624)Search more codes in this manual