Indramat · CLM01.3-M Flying Cutoff Control
The input power required by the drives from the Indramat HVE or HVR power supply unit is excessive. This condition indicates that the combined power demand during acceleration or sustained operation exceeds the supply unit's capability, and the error will be stored for no more than 500 ms.
Click steps to track your progress.
Reduce the allowable acceleration times for the connected drives in the application parameters to lower peak power demand.
Evaluate if the Indramat HVE or HVR power supply unit is appropriately sized for the combined peak power demand of all connected drives.
Consider using a drive controller with a smaller peak current capacity if the current setup is oversized for the motor load.
Inspect the mechanical system for any binding, excessive friction, or unexpected load increases that could be demanding more power.