The Indramat HVE or HVR power supply unit cyclically sends status and error messages via a serial connection to the connected controller (DIAX04 SSE-03VRS). This warning is generated if the controller does not receive several sequential messages, indicating a communication breakdown.
Click steps to track your progress.
Visually inspect the serial bus cable connecting the HVE/HVR power supply unit to the DIAX04 SSE-03VRS controller for any signs of damage or loose connections.
Check the termination and continuity of the bus cable, and replace it if necessary.
If the bus cable and connections are verified, consider replacing the HVE/HVR power supply unit if its serial interface is suspected to be defective.
If the fault persists after checking the cable and power supply, the serial interface of the DIAX04 SSE-03VRS controller may be defective, requiring controller replacement.