EL
ErrorLib
Brands
||
  1. Home
  2. Indramat
  3. CLM01.3-M Flying Cutoff Control
  4. F246
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

F246

Max signal frequency of encoder 2 exceeded

Indramat · CLM01.3-M Flying Cutoff Control

What does F246 mean?

The signal frequency of the optional encoder (encoder 2) has exceeded the maximum allowed frequency of the encoder interface. If P-0-0185 (Function of encoder 2) is set to 4 (spindle encoder), only the position status of the optional encoder is cleared to 0. Otherwise, F246 is generated, and the position status is cleared to 0.

Common Causes

  • Encoder speed is too high for the selected encoder type or the interface limits of the Indramat DIAX04 SSE-03VRS drive controller.
  • Incorrect encoder resolution configured in parameters, leading to an artificially high signal frequency.
  • Incorrect parameter P-0-0185 setting not matching the application (e.g., not set for spindle encoder when it should be).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the maximum permissible signal frequency for the Indramat DIAX04 SSE-03VRS encoder interface and the specific encoder 2 model used.

  2. 2

    Check the mechanical speed of the motor or spindle connected to encoder 2. Ensure it does not exceed the maximum operational speed specified for the encoder.

  3. 3

    Review the encoder resolution and scaling parameters in the Indramat DIAX04 SSE-03VRS drive controller. Correct any settings that may cause an erroneously high calculated signal frequency.

  4. 4

    Examine parameter P-0-0185 (Function of encoder 2). If encoder 2 is used as a spindle encoder, ensure this parameter is set to 4. Adjust the parameter if it's incorrect for the application.

  5. 5

    Consider using an encoder with a lower resolution if the mechanical speed cannot be reduced, or if the current encoder's resolution and the drive's interface limits are incompatible.

Browse all codes in this manual (31)
Verified technical data. Last updated: April 2026

Related Faults

E219Warning Drive temp. surveillance defectiveE221Warning Motor temp. surveillance defectiveE225Motor overload
Source: Indramat CLM01.3-M Flying Cutoff Control
Open Manual (Page 33)Search more codes in this manual