Indramat · CLM01.3-M Flying Cutoff Control
With HVR power supply units only! This fault indicates an overcurrent condition within the Indramat HVR power supply unit, potentially caused by a short circuit in the power supply unit itself, a connected drive controller, the motor, or the motor cable.
Click steps to track your progress.
De-energize the Indramat HVR power supply unit and ensure all power is locked out.
Systematically disconnect the power supply lines to individual Indramat DIAX04 SSE-03VRS drive controllers connected to the HVR unit, one at a time.
Check the power cables and motor windings for each drive controller and motor for short circuits or ground faults using a multimeter or insulation tester.
Re-energize the HVR unit, reconnecting drive controllers one by one, to isolate the specific component causing the overcurrent fault.
If the fault persists with all loads disconnected, the short circuit is likely internal to the HVR power supply unit, requiring its replacement.