Indramat · CLM01.3-M Flying Cutoff Control
With HVE power supply units only! At least one phase of the 3-phase power supply input to the HVE unit is missing, indicating a loss of input power similar to F381 but specific to HVE units.
Click steps to track your progress.
Verify the incoming 3-phase power supply at the input terminals of the Indramat HVE power supply unit using a multimeter. Confirm all three phases are present and balanced.
Inspect all upstream mains fuses and circuit breakers for the power supply unit. Replace any blown fuses or reset tripped breakers.
Check power contactors and their auxiliary contacts for proper operation and engagement in the power distribution circuit.
Inspect all power wiring connections from the mains supply to the HVE unit for looseness, damage, or disconnections.