Indramat · CLM01.3-M Flying Cutoff Control
With HVR power supply units only! The mains voltage exceeds permissible tolerances of 3x 380...480V, ± 10%. This fault occurs when the incoming supply voltage is outside the acceptable operating range for the Indramat HVR power supply unit.
Click steps to track your progress.
Measure the incoming line voltage (phase-to-phase) at the input terminals of the Indramat HVR power supply unit (X1/L1, X1/L2, X1/L3).
Verify the measured voltage is consistently within the specified range of 3x 380...480V, ± 10%.
If the voltage is outside the range, check the upstream power distribution system for issues or ensure a correctly sized and configured matching transformer is used.
Consult the power utility if persistent voltage fluctuations or incorrect supply levels are detected on the main supply.