EL
ErrorLib
Brands
||
  1. Home
  2. Indramat
  3. CLM01.3-M Flying Cutoff Control
  4. F401
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

F401

Double MST failure shutdown

Indramat · CLM01.3-M Flying Cutoff Control

What does F401 mean?

The master sync telegram (MST) was not received by the Indramat DIAX04 SSE-03VRS drive controller in two successive SERCOS cycles, indicating a communication breakdown in the SERCOS fiber optic ring.

Common Causes

  • Disruption in the Fiber Optic transmission line.
  • Too much attenuation of the light signal in the Fiber Optic cable.
  • Malfunction in the SERCOS interface module of the drive controller (general).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Visually inspect all Fiber Optic connections and cables in the SERCOS ring for physical damage, kinks, or improperly seated connectors. Ensure all connectors are clean.

  2. 2

    Measure the optical power attenuation across each segment of the Fiber Optic cable using an appropriate optical power meter. Verify that the attenuation between TX and RX for any connection does not exceed 12.5 dB.

  3. 3

    Check the status indicators (LEDs) on the SERCOS interface modules of all devices in the ring for any indications of link loss or communication errors.

  4. 4

    If communication issues persist despite good cable integrity and attenuation, consider replacing the SERCOS interface module in the affected Indramat DIAX04 SSE-03VRS drive controller.

Browse all codes in this manual (31)
Verified technical data. Last updated: April 2026

Related Faults

E219Warning Drive temp. surveillance defectiveE221Warning Motor temp. surveillance defectiveE225Motor overload
Source: Indramat CLM01.3-M Flying Cutoff Control
Open Manual (Page 39)Search more codes in this manual