F434

Emergency-Stop

Indramat · CLM01.3-M Flying Cutoff Control

What does F434 mean?

The emergency stop switch (E-Stop) has been pressed, causing the drive to perform the emergency stop function selected in P-0-0119 (Best possible deceleration). Setting bit 15 of S-0-0011 (Class 1 diagnostics) also causes an error message to be issued to the controller.

Common Causes

  • The emergency stop switch has been pressed.
  • A fault in the E-Stop circuit is simulating an E-Stop activation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Identify and verify that all emergency stop buttons and safety gates in the system are released and in their normal, unactuated state.

  2. 2

    Inspect the wiring of the emergency stop circuit for any short circuits or faults that might simulate an E-Stop activation, checking continuity and insulation.

  3. 3

    Verify the functionality of the emergency stop relays and safety modules (if present) by checking their input and output statuses.

  4. 4

    Ensure parameter P-0-0119 (Best possible deceleration) in the Indramat DIAX04 SSE-03VRS drive controller is set appropriately for the application's safety requirements.

  5. 5

    Once the cause of activation is resolved, acknowledge and clear the error from the Indramat DIAX04 SSE-03VRS drive controller.