The DIAX04 SSE-03VRS drive's primary encoder (Encoder 1) has detected an invalid sequence or state in its quadrature signals (A, B channels). This indicates a problem with the encoder's signal generation or the wiring, resulting in an unreliable position or velocity feedback. The drive faults to prevent incorrect motor control or machine positioning.
Click steps to track your progress.
Inspect the encoder 1 cable for any physical damage, kinks, or crushing. Verify continuity and check for shorts between signal lines and ground.
Check all connections at both the encoder and the DIAX04 SSE-03VRS drive for looseness, corrosion, or incorrect wiring.
Verify the encoder supply voltage at the encoder connector. Ensure it is stable and within the encoder's specified range.
Monitor the encoder A/B signals using an oscilloscope, if possible, to check for clean quadrature signals without dropouts or noise.
Ensure proper shielding and grounding of the encoder cable to minimize electrical interference. If the issue persists, consider replacing encoder 1.