Indramat · DIAX 04
The DIAX04 SSE-03VRS drive's power supply for the travel limit switches has an error. This means the voltage supply to the limit sensors is out of specification, missing, or there is an overload/short circuit on the output. This compromises critical safety functions, as the drive cannot reliably detect axis travel limits, risking mechanical damage or injury.
Click steps to track your progress.
Disconnect all travel limit switch wiring from the DIAX04 SSE-03VRS drive inputs. If the fault clears, the issue is external.
Measure the voltage at the limit switch power supply output terminals on the DIAX04 SSE-03VRS. Verify it's within specification (e.g., 24VDC).
Check the wiring to each limit switch for shorts to ground or power, and for continuity.
Test each limit switch for proper operation and current draw. Replace any faulty switches.
If the fault persists even with switches disconnected, there may be an internal fault with the DIAX04 SSE-03VRS drive's input power supply circuit.