Indramat · DIAX 04
The DIAX04 SSE-03VRS drive's power supply for the Emergency-Stop (E-Stop) circuit has an error. This signifies that the voltage supply for the E-Stop monitoring is faulty or an overload/short circuit is detected. This is a critical safety fault, as the E-Stop function cannot be guaranteed, requiring immediate shutdown to ensure personnel and machine safety.
Click steps to track your progress.
Disconnect all E-Stop related wiring from the DIAX04 SSE-03VRS drive's safety input. If the fault clears, the issue is external.
Measure the voltage at the E-Stop circuit power supply output terminals on the DIAX04 SSE-03VRS. Verify it's within specification (e.g., 24VDC).
Check the E-Stop wiring for shorts to ground or power, and for continuity. Inspect E-Stop buttons and safety relays for proper function.
Isolate external safety components one by one to identify the faulty device or wiring section.
If the fault persists even with external wiring disconnected, there may be an internal fault with the DIAX04 SSE-03VRS drive's safety input power supply circuit.