Indramat · DIAX 04
The DIAX04 SSE-03VRS power supply unit has detected a short circuit to ground on one of its outputs or internal circuits. This is a severe fault indicating insulation breakdown or incorrect wiring, leading to uncontrolled current flow and potential damage to the unit or connected equipment. The unit shuts down immediately for safety.
Click steps to track your progress.
Immediately disconnect all output power cables from the DIAX04 SSE-03VRS power supply unit (e.g., DC bus connections) and attempt to power up. If the fault clears, the short is external.
Use an insulation resistance tester (megger) to check for shorts to ground on the DC bus bars and connected cables.
Inspect all power wiring and connections for any signs of damage, pinching, or contact with the enclosure ground.
Check for moisture, debris, or carbonization within the DIAX04 SSE-03VRS power supply unit and its terminal connections.
If the fault persists with no external connections, it indicates an internal short to ground within the DIAX04 SSE-03VRS power supply unit, requiring factory service or replacement.