F401

Double MST failure shutdown

Indramat · DIAX 04

What does F401 mean?

The DIAX04 SSE-03VRS drive detected a double failure of the Master Synchronization Telegram (MST) within its real-time communication network (e.g., Sercos). This means the drive has lost synchronization with the master controller twice consecutively. This is a critical communication fault that results in immediate shutdown to prevent uncoordinated and potentially dangerous movements.

Common Causes

  • Repeated interruptions or severe degradation of the real-time communication link (e.g., fiber optic cable, Sercos ring) to the DIAX04 SSE-03VRS drive.
  • Master controller experiencing issues generating or transmitting the MST.
  • Faulty communication interface or hardware on the DIAX04 SSE-03VRS drive.
  • Incorrect network configuration or timing parameters (e.g., S-0-0010) causing synchronization loss.
  • Excessive electromagnetic interference impacting communication signal integrity.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the communication cable (e.g., fiber optic, Ethernet) connecting the DIAX04 SSE-03VRS drive to the master controller. Check for physical damage, proper termination, and secure connections.

  2. 2

    Verify the status of the master controller's communication interface and its ability to transmit MSTs.

  3. 3

    Check communication ring integrity (if applicable) for breaks or faulty nodes. Bypass or isolate sections to identify the problematic segment.

  4. 4

    Review and verify communication parameters (e.g., S-0-0010, S-0-0011) in the DIAX04 SSE-03VRS drive and the master controller for consistency.

  5. 5

    Monitor communication diagnostic indicators on both the master and the DIAX04 SSE-03VRS. If the fault persists, consider a faulty communication interface on the drive.

Browse all codes in this manual (60)