F629

Positive travel limit exceeded

Indramat · DIAX 04

What does F629 mean?

The DIAX04 SSE-03VRS drive has detected that the machine axis has moved beyond its configured positive software travel limit. This is a safety and machine protection fault, indicating that the axis is outside its allowed operating range, potentially risking mechanical damage or collision. The drive attempts to stop motion safely.

Common Causes

  • Incorrectly configured positive software travel limit (e.g., S-0-0049) in the DIAX04 SSE-03VRS drive.
  • Commanded position exceeded the positive software limit due to an error in the motion profile or control program.
  • Faulty position feedback (encoder) providing incorrect position data, making the drive miscalculate its actual position.
  • Mechanical system failure or excessive inertia causing overshoot beyond the commanded limit.
  • Ignoring or overriding limit switch signals incorrectly.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Manually move the machine axis back into the allowed travel range, ensuring no mechanical obstructions.

  2. 2

    Verify and adjust the positive software travel limit parameter (e.g., S-0-0049) in the DIAX04 SSE-03VRS drive to match the actual mechanical limits.

  3. 3

    Review the motion program or commands to ensure no position setpoints exceed the defined limits.

  4. 4

    Inspect the motor encoder and its wiring for proper function and accurate position feedback.

  5. 5

    Check the physical positive limit switch for functionality and correct activation, ensuring it is not bypassed or faulty.