Indramat · IndraDrive MPx02
The IndraDrive MPx02 has detected an undervoltage condition within its internal power section, specifically on the DC bus. This means the DC link voltage has fallen below a safe operating threshold, which can occur due to insufficient incoming AC power or excessive current demand, impacting drive stability.
Click steps to track your progress.
Measure the incoming AC mains voltage at the drive input and verify it is within the specified operating range, ensuring no upstream issues are causing low supply voltage.
Monitor the DC bus voltage (if accessible via diagnostics) to confirm the undervoltage condition and its behavior during operation.
Check all power connections to the IndraDrive MPx02 for looseness or corrosion, which could introduce resistance and voltage drops.
Verify the drive's configured mains voltage parameter (P-0-0120) matches the actual supply voltage.
If the mains voltage is stable and correct, but undervoltage persists, it may indicate an internal fault within the drive's power section, requiring service.