Indramat · IndraDrive MPx02
The IndraDrive MPx02 has detected that the starting lockout has not been activated within the specified time interval defined by parameter P-0-0103 (Time interval of forced dynamization). This indicates a potential safety-related issue if the lockout is not engaged as required, possibly allowing unintended startup.
Click steps to track your progress.
Verify the setting of parameter P-0-0103 (Time interval of forced dynamization) and ensure it is appropriate for the application's operating cycle and safety requirements.
Confirm that the control logic (PLC or master controller) is correctly activating the starting lockout within the specified time interval.
Review the sequence of operations for activating starting lockout to ensure it is performed in the correct order and timing.
If the interval is too short for the application's process, adjust P-0-0103 to a value that allows sufficient time for the starting lockout to be activated.