Indramat · IndraDrive MPx02
An error occurred during the index check in the multiplex channel of the IndraDrive MPx02. During cyclic data exchange, the index used to access "Data container A: configuration list command value-x" points to a non-initialized position in the list, causing data access issues.
Click steps to track your progress.
Check the configuration settings for "Data container A: configuration list command value-x" in the IndraDrive MPx02 to ensure it is properly initialized and contains valid data.
Verify the low byte of parameter S-0-0368 (Data container A: addressing) to ensure it is pointing to a valid, initialized position within the data container.
Review the application logic that writes to or reads from "Data container A" via the multiplex channel for any out-of-bounds addressing attempts.
Consult the functional description of the firmware for "Multiplex Channel" for detailed information on proper configuration and addressing of data containers.
Perform a drive reset and re-download the configuration if data corruption is suspected.