Indramat · IndraDrive MPx02
An excessive current flow has been detected in the power section of the IndraDrive MPx02, exceeding the drive's internal limits. This is a fatal error, leading to an immediate torque-free shutdown to protect the drive and motor from damage.
Click steps to track your progress.
Immediately de-energize the drive and inspect the motor and motor cables for any visible damage, insulation breaches, or loose connections.
Measure the insulation resistance between motor phases (U-V, V-W, U-W) and from each phase to ground using a megohmmeter (e.g., at 500VDC); expect >1 MΩ.
Check motor winding resistance between phases for consistency and compare with motor specifications to detect internal shorts.
Verify that all motor parameters, especially P-0-0504 (Motor Nominal Current), are correctly configured in the drive to match the motor nameplate data.
Inspect the mechanical system for any binding, obstructions, or excessive load that could cause the motor to draw abnormally high current.