F380

Short to ground power supply unit

Indramat · CLM01.3-M Flying Cutoff Control

What does F380 mean?

This fault indicates a ground short within the power supply unit, a connected Indramat DIAX04 SSE-03VRS drive controller, the motor, or the motor cable, leading to an unsafe condition or current imbalance.

Common Causes

  • Ground short in the power supply unit itself.
  • Ground short in a connected drive controller.
  • Ground short in the motor or the motor cable.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    De-energize the power supply unit and all connected drive components, and apply lockout/tagout procedures.

  2. 2

    Disconnect the motor power cables from the drive controller. Perform insulation resistance tests (megger) on each motor phase to ground and phase-to-phase, expecting resistance >1 MΩ.

  3. 3

    Disconnect the power cables from the Indramat DIAX04 SSE-03VRS drive controller to the power supply unit. Perform insulation resistance tests on the drive controller's output terminals to ground.

  4. 4

    Systematically reconnect components one at a time, energizing between steps, to isolate the component causing the ground fault.

  5. 5

    If the ground fault persists with all external connections removed, the fault is likely internal to the Indramat power supply unit, requiring its replacement.

Browse all codes in this manual (31)
Verified technical data. Last updated: March 2026