Overcurrent in power section
Indramat · Indradrive
What does F8060 mean?
A sudden surge of current exceeding the instantaneous rating was detected in the IndraDrive's power section, leading to an immediate shutdown to prevent damage. This is often caused by a short circuit in the motor or cabling, or a rapid acceleration of a high inertia load.
Common Causes
- Short circuit between motor phases or between a phase and ground in the motor or motor cable.
- Rapid acceleration or deceleration of a high inertia load without adequate ramp times.
- Incorrect motor parameters causing an unstable current loop.
- Drive power section hardware failure (e.g., IGBT short).
Repair Steps & Checklist
Click steps to track your progress.
- 1
Disconnect power and perform insulation resistance tests (megger) between motor phases and to ground on both the motor and motor cable.
- 2
Verify that the acceleration and deceleration ramps (e.g., S-0-0077 Ramp Time Pos, S-0-0078 Ramp Time Neg) are appropriately set for the application's inertia.
- 3
Check motor parameters in the drive (e.g., S-0-0010 Motor Nominal Current, S-0-0013 Motor Type) against the motor nameplate.
- 4
Inspect the motor and mechanical system for any binding or sudden impacts.
- 5
If the motor and cabling are verified good, the drive's power section may be faulty and require replacement.