Indramat · ServoDyn D Servo Drive
This error occurs if the optional IDS board is enabled via Parameter 80 (Serial Interface) but the CLM01.3-M fails to detect a physical connection to the IDS board. This indicates a communication or hardware issue with the IDS board.
Click steps to track your progress.
Verify the physical connection of the IDS board to CLM01.3-M connector X6, ensuring the IKS 742 cable is securely attached and undamaged.
Check the length and integrity of the IKS 742 cable; replace it if it is defective or exceeds the maximum recommended length of 10 meters.
Review Parameter 80 (Serial Interface) and disable the IDS board if it is not installed or intended for use.
Ensure the IDS board is properly seated in its slot within the CLM01.3-M chassis.
If the issue persists, contact Indramat Service Department as it may indicate a fault with the IDS board or the CLM01.3-M serial communication port.