Indramat · ServoDyn D Servo Drive
This error occurs when the CLM01.3-M's back-up battery, responsible for retaining parameters when power is off, is disconnected or has low voltage. This results in the loss of critical configuration parameters, indicated by asterisks (*) on the display.
Click steps to track your progress.
Turn OFF power to the CLM01.3-M.
Remove the MOK 11 card (Memory and Battery Module) as shown in Figure 2.3 of the manual.
Replace the 3.6-volt lithium back-up battery on the MOK 11 card.
After replacing the battery, turn power ON and re-enter all necessary CLM01.3-M parameters, as they will have been lost (refer to Chapter 4).
Verify that all CLM01.3-M parameters are stored with valid numbers (no asterisks) and correspond to the application's requirements.