Indramat · ServoDyn D Servo Drive
This error occurs when the CLM01.3-M's back-up battery, which stores the user program when power is off, is disconnected or has low voltage. This leads to the loss of the application program, requiring re-entry or restoration.
Click steps to track your progress.
Turn OFF power to the CLM01.3-M.
Remove the MOK 11 card (Memory and Battery Module) as shown in Figure 2.3 of the manual.
Replace the 3.6-volt lithium back-up battery on the MOK 11 card.
After replacing the battery, turn power ON and reload the user program into the CLM01.3-M (refer to Chapter 5).
Verify that all CLM01.3-M program blocks are correctly entered and functional after restoration.