EL
ErrorLib
Brands
||
  1. Home
  2. Indramat
  3. ServoDyn D Servo Drive
  4. 40
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

40

Battery Is Low

Indramat · ServoDyn D Servo Drive

What does 40 mean?

This condition occurs when the lithium back-up battery, located on the MOK 11 card, which is responsible for retaining CLM01.3-M memory (programs, parameters, counter status) during power OFF, falls below its minimum voltage level.

Common Causes

  • The 3.6-volt lithium back-up battery is depleted or has critically low voltage.
  • The back-up battery is disconnected or poorly seated on the MOK 11 card.
  • Faulty MOK 11 card preventing proper battery charging or monitoring.
  • Prolonged power off periods, leading to battery drainage.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Turn OFF all power to the CLM01.3-M.

  2. 2

    Carefully remove the Memory and Battery Module (MOK 11 card) from its slot (refer to Figure 2.3 in the manual).

  3. 3

    Replace the 3.6-volt lithium battery with a new, compatible replacement.

  4. 4

    After battery replacement, all parameters and program data will be lost; re-enter them from a backup or manually (refer to Chapters 4 and 5).

  5. 5

    Ensure the new battery is securely installed and the MOK 11 card is properly re-seated.