Indramat · ServoDyn D Servo Drive
This condition occurs when the lithium back-up battery, located on the MOK 11 card, which is responsible for retaining CLM01.3-M memory (programs, parameters, counter status) during power OFF, falls below its minimum voltage level.
Click steps to track your progress.
Turn OFF all power to the CLM01.3-M.
Carefully remove the Memory and Battery Module (MOK 11 card) from its slot (refer to Figure 2.3 in the manual).
Replace the 3.6-volt lithium battery with a new, compatible replacement.
After battery replacement, all parameters and program data will be lost; re-enter them from a backup or manually (refer to Chapters 4 and 5).
Ensure the new battery is securely installed and the MOK 11 card is properly re-seated.