1018

LOGIC FAILURE #2

Kone · Elevator Control

What does 1018 mean?

A logic failure of type #2 has occurred in the motor controller (codes 1018, 2018, 3018). This indicates an internal control logic error, preventing correct operation. The specific lift reaction is controller dependent.

Common Causes

  • Internal controller logic processing error.
  • Corrupted program memory or runtime data.
  • Hardware fault affecting logic circuits or CPU functionality.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the motor controller's power supply voltages (AC input and DC bus) are within specified limits.

  2. 2

    Check all motor controller configuration parameters and application software settings against the latest backup or approved documentation.

  3. 3

    Inspect all signal and feedback cabling, including motor encoder, for loose connections, damage, or electromagnetic interference.

  4. 4

    Perform a controlled power cycle of the motor controller and observe restart behavior.