Kone · Elevator Control
The motor controller (codes 1038, 2038, 3038) has detected that the main contactor is open when it should be closed. This indicates a contactor control issue, preventing power to the motor. The specific lift reaction is controller dependent.
Click steps to track your progress.
Verify the output signal from the motor controller to the main contactor coil for presence and correct voltage.
Measure the voltage across the main contactor coil terminals while the controller attempts to close it, comparing against nominal coil voltage.
Inspect the main contactor's auxiliary contacts for proper mechanical operation and continuity when the contactor is commanded closed.
Check all wiring connections related to the main contactor, including power, control, and feedback circuits, for looseness, corrosion, or damage.
Verify relevant motor controller parameters pertaining to contactor control and feedback for correct configuration.